Installation
12/00 UDC2300 Controller Product Manual 17
9
10
5+
4-
Control Relay #2
Motor
Power
Supply
Close (CCW)
Open (CW)
Control
Relay #1
24864
Alarm #2 is not available with Three Position Step Control.
1
2 amp Fast Blo
1
See Figure 2-15 for Alarm and Duplex Output Connections.
Figure 2-14  Three Position Step Control Connections
9
10
11
12
1 2
Load
Supply
Power
Control or Alarm
Relay #2 Load
Alarm
Relay #1 Load
Load
Supply
Power
5 amp fast Blo
5 amp Fast Blo
24867
Control relays 1 and 2 are configured N.O. as shipped. Alarm relays 1
and 2 are configured N.C. as shipped. N.O. or N.C. configurations are
selectable by jumpers on main printed wiring boards. See “Preliminary
Checks” in this sections of the Product Manual for details. Each SPST
relay is rated at 5 A, 120 Vac and 24 Vdc, 2.5 A, 240 Vac.
Alarm #2 not available for Time Proportional Duplex or Three Position
Step Control.
1
1
2
Figure 2-15  Alarm and Duplex Output Connections