Configuration
32 UDC2300 Controller Product Manual 12/00
4.8 Algorithm Set Up Group
Introduction
This data deals with various algorithms in the controller: Control algorithm, Output
algorithm, Current Duplex Range, and Relay Cycle Time Increment.
Function Prompts
Table 4-7 ALGOR Group (Numeric Code 500) Function Prompts
Prompt Selection or Range of Setting
English Numeric
Code
Description
Numeric
Code
English
Factory
Setting
Reference
Guide
Page
CTRALG 501
Control
Algorithm
0
1
2
3
4
ONOF
PIDA
PIDB
PDMR
TPSC (3 position step)
PIDA 127
OUTALG 502
Output
Algorithm
0
1
2
3
4
5
6
7
RLY (Time simplex Relay 1)
RLY2 (Time simplex Relay 2)
CUR (Current simplex)
TPSC (3 Position step)
RLYD (Time duplex)
CURD (Current duplex)
CURT (Current/time duplex)
TCUR (Time/current duplex)
depends
on
model
142
4-20RG 503
Current Duplex
Range
0
1
100 (Full)
50 (Split)
100 119
RLY TYP 504
Relay Cycle
Time Increment
0
1
MECH (one sec. increments)
S S (1/3 sec increments)
MECH 149