Installation
16 UDC2300 Controller Product Manual 12/00
Installing a current output instrument
into a case wired for relay outputs
will damage the instrument.
CAUTION
5
4
Controller
Load
0 to 750 Ohms
+
-
24862
1
Connect shield to ground at one end only.
3
Set output jumper per Figure 2-2.
Current
output
4 to 20 mA
2
1
2
See Figure 2-15 for Alarm and Duplex Output Connections.
See Table 2-3 and Table 2-4 for Control and Alarm Relay Contact
information.
Figure 2-12 Current Output
Solid State
10 Amp Solid State
Relay Assembly
5-
4+
L2 / N
L1
LOAD
L1/H
L2/N
+
-
Green
White
Black
Relay
Assembly
24863R
AC
This Solid State relay is rated at 15 Amps at 25°C, linearly derated
to 10 Amps at 55°C.
Customer should size fuse accordingly
1
1
10 amp Fast Blo
Green
Black
White
OUTPUT1 OUTPUT2
9-
10+
L2 / N
L1
Figure 2-13 External Solid State Relay Option (Internal Open Collector Output)