Configuration
34 UDC2300 Controller Product Manual 12/00
Table 4-8 INPUT1 Group (Numeric Code 600) Function Prompts, continued
Prompt Selection or Range of Setting
English Numeric
Code
Description
Numeric
Code
English
Factory
Setting
Reference
Guide
Page
IN1 HI 605
Input 1 High
Range Value
−999 to 9999 floating in
engineering units
2400 136
IN1 LO 606
Input 1 Low Range
Value
−999 to 9999 floating in
engineering units
0 137
RATIO1 607
Ratio on Input 1 -20.0 to 20.0 1.00 149
BIAS 1 608
Bias on Input 1 -999 to 9999 0.0 125
FILTR1 609
Filter for Input 1 0 to 120 seconds
0 = No Filter
1.0 134
BRNOUT 610
Burnout Protection
(Sensor Break)
0
1
2
3
NONE
UP (Upscale)
DOWN (Downscale)
NOFS (No Failsafe)
UP 126
EMISS 611
Emissivity 0.01 to 1.00 (RADH &
RADI only)
1.0 133
FREQ 612
Power Line
Frequency
0
1
60
50
60 135
DISPLY 613
Defalut Display
(Single Display
models only)
0
1
2
SP (Setpoint)
PRY ( PV with Label)
PRN (PV without Label)
PRN —
LNGUAG 614
Language
Selection
0
1
2
3
4
5
ENGL
FREN
GERM
SPAN
ITAL
NUMB (Numeric)
ENGL 140