Function Parameter Reference Guide
138 UDC2300 Controller Product Manual 12/00
12.2.49 IN1TYP (INPUT 1 ACTUATION TYPE)
This prompt is part of the Input 1 Set up group.
This selection determines what actuation you are going to use for Input 1.
ATTENTION
Changing the input type will result in the loss of Field Calibration values and will restore Factory
Calibration values.
Selections Definitions
B
E H
E L
J H
J L
K H
K L
NNMH
NNML
N90H
N90L
NIC
R
S
T H
T L
W H
W L
100H
100L
200
500
RADH
RADI
0-20
4-20
10m
50m
0-5
1-5
0-10
100m
B—B Thermocouple
E H—E Thermocouple High
E L—E Thermocouple Low
J H—J Thermocouple High
J H—J Thermocouple Low
K H—K Thermocouple High
K H—K Thermocouple Low
NNMH—Ni-Ni-Moly Thermocouple High
NNML—Ni-Ni-Moly Thermocouple Low
N90H—NiMo-NiCo Thermocouple High
N90L—NiMo-NiCo Thermocouple Low
NIC—Nicrosil-Nisil Thermocouple
R—R Thermocouple
S—S Thermocouple
T H—T Thermocouple High
T L—T Thermocouple Low
W H—W5W26 Thermocouple High
W L—W5W26 Thermocouple Low
100H—100 Ohm RTD High
100L—100 Ohm RTD Low
200—200 Ohm RTD
500—500 Ohm RTD
RADH—Radiamatic RH
RADI—Radiamatic RI
0-20—0 to 20 Milliamperes
4-20—4 to 20 Milliamperes
10m—0 to 10 Millivolts
50m—0 to 50 Millivolts
0-5—0 to 5 Volts
1-5—1 to 5 Volts
0-10—0 to 10 Volts
100m—0 to 100 Millivolts