Function Parameter Reference Guide
12/00 UDC2300 Controller Product Manual 145
12.2.66 PBorGN (PROPORTIONAL BAND UNITS)
This prompt is part of the Control Set up group.
Select one of the following for the Proportional (P) term of the PID algorithm:
Selections Definitions
PB PROPORTIONAL BAND Selects units of percent proportional band
for the P term of the PID algorithm.
Where: PB % = 100 %
GAIN
GAIN GAIN selects the unitless term of gain for the P term of the PID
algorithm.
Where: GAIN = 100 %
PB %
12.2.67 PERIOD (TIMEOUT PERIOD)
This prompt is part of the Timer Set up group.
This selection allows you to configure a Time-out period
Range of Setting:0.00 to 99:59 (Hours:Minutes)
12.2.68 PG END (PROGRAM TERMINATION STATE)
This prompt is part of the Setpoint Ramp/Program Set up group.
The program termination state function determines the status of the controller upon
completion of the program.
Selections Definitions
LAST
Hold at last Setpoint in program
FSAF
Manual Mode/Failsafe Output