Function Parameter Reference Guide
154 UDC2300 Controller Product Manual 12/00
12.2.93 SPPROG (SETPOINT RAMP/SOAK PROGRAM)
This prompt is part of the Setpoint Ramp/Program Set up group.
This selection allows you to disable/enable the Setpoint Ramp/Soak Program function.
“SPRAMP” and “SPRATE” must be disabled.
Selections Definitions
DIS
Disables the Ramp/Soak Program Function. Allows “SPRAMP” or
“SPRATE” option to be selected.
ENAB
Enables the setpoint Ramp/Soak Program Function.
12.2.94 SPRAMP (SINGLE SETPOINT RAMP)
This prompt is part of the Setpoint Ramp/Program Set up group.
This selection allows you to disable/enable the Setpoint Ramp function.
Make sure you configure a ramp time (TI MIN) and a final setpoint value (FINLSP).
“SPPROG” and “SPRATE” must be disabled.
Selections Definitions
DIS
Disables the Setpoint Select Function. Allows “SPPROG” or “SPRATE”
option to be selected.
ENAB
Enables the Setpoint Select Function.
12.2.95 SPRATE (SETPOINT RATE)
This prompt is part of the Setpoint Ramp/Program Set up group.
This selection allows you to configure a specific rate of change for any local setpoint
change.
“SPRAMP” and “SPPROG” must be disabled
Selections Definitions
DIS
Disables the Setpoint Rate option.
ENAB
Enables the Setpoint Rate option. SP Rate parameters
(EUHRUP, EUHRDN) appear when Rate is enabled.