Function Parameter Reference Guide
156 UDC2300 Controller Product Manual 12/00
12.2.100 STRSEG (START SEGMENT)
This prompt is part of the Setpoint Ramp/Program Set up group.
The start segment number designates the number of the first segment.
Range of Setting: 1 to 11
12.2.101 SW VAL (AUTOMATIC SWITCHOVER VALUE)
This prompt is part of the Control Set up group.
This is the value of Process Variable or Setpoint at which the controller will switch from
Tuning Constant Set #2 to Set #1.
Only appears when PIDSET selection is configured for either 2 PV or 2 SP.
Range of Setting: Value in engineering units within PV or SP range limits
12.2.102 TI MIN (SINGLE SETPOINT RAMP TIME)
This prompt is part of the Setpoint Ramp/Program Set up group.
Enter the number of minutes desired to reach the final setpoint of a single setpoint ramp.
•A ramp time of “0” implies an immediate change of setpoint to the final setpoint.
Range of Setting: 0 to 255 minutes
12.2.103 TIMER (TIMER OPTION)
This prompt is part of the Timer Set up group.
This selection enables or disables a configured Time-out period.
Selections Definitions
ENAB
Enables the Timer option.
DIS
Disables the Timer option.
12.2.104 ToBEGN (RESET PROGRAMMING TO BEGINNING)
This prompt is part of the Setpoint Ramp/Program Set up group.
This selection enables or disables programming reset.
Selections Definitions
DIS
Disables programming reset.
KEY
Allows programming reset from the keyboard.