See the HPE StoreVirtual 3200 Management Console Online Help for more information.
Replacing a drive enclosure I/O module
Verify I/O module failure
Before replacing an I/O module, verify its status using one of the following methods:
• Ensure that the I/O module has failed by verifying the I/O module status LEDs. For the location of the
I/O module LEDs, see HPE StoreVirtual 3200 drive enclosure on page 12. For information on
interpreting the status, see "Related reference".
• Verify the I/O module status from the hardware report in the StoreVirtual Management Console.
More information
Status LED descriptions on page 15
Removing an I/O module
Procedure
1. Unplug all cables from the I/O module.
a. Do not unplug the power cables if performing a hot or warm swap.
b. If SAS cables are being used to connect enclosures and you must disconnect from the affected
enclosure, be sure that you do not remove both SAS cables at the same time. At least one SAS
cable must be connected to the component to ensure access continues to the drives in the
enclosure.
2. Loosen the captive retaining thumbscrew (1), and swing out the I/O module handle (2).
3. Pull the I/O module (3) out of the enclosure using the I/O module handle.
94 Replacing a drive enclosure I/O module