Item Method Expected Result Troubleshooting
Availability
of the fusion
module
actuator and
skylight
magnetic
lock
On the ECC800-
Pro WebUI,
choose
Monitoring >
Aisle > Fusion
Module Actuator
Group > Fusion
Module
Actuator. On the
Running Control
page, remotely
open the skylight.
NOTE
If you open the
skylight remotely
for maintenance,
manually close the
skylight after the
maintenance is
complete.
The fusion module
actuator controls
the skylight in the
aisle of the smart
module.
If the skylight cannot
be normally
controlled, check
whether the cable
between the skylight
magnetic lock and
fusion module
actuator is in good
condition and
securely connected. If
the fault persists,
replace the skylight
magnetic lock or
fusion module
actuator.
Availability
of the access
actuator
On the ECC800-
Pro WebUI,
choose
Monitoring >
Aisle > Access
Actuator Group
> Access
Actuator. On the
Running Control
page, remotely
open doors.
The access actuator
can be used to
open the aisle doors
of the smart
module.
If an aisle door
cannot be normally
controlled, check
whether the
magnetic lock cable
is loose or
disconnected. If so,
reconnect the cable.
If not, replace the
access actuator or
magnetic lock.
Availability
of the access
control
system
Press the exit
button to open
the door.
The door can be
opened by pressing
the exit button.
If the door cannot be
opened by pressing
the exit button after
other devices in the
access control system
are normal, replace
the exit button.