Item Method Expected Result Troubleshooting
Availability
of the smart
rPDU
Observe the
indicator of the
smart rPDU
switch.
The indicator of the
smart rPDU switch
is on.
If the switch indicator
is o, check the
branch load. After
checking that the
branch is not
overloaded, replace
the smart rPDU if the
switch indicator is
still
o.
Aisle door
availability
Check whether
the door can be
opened and
closed smoothly.
The door can be
opened and closed
smoothly.
If the door cannot be
opened or closed
smoothly, check the
rail for obstacles and
clear the obstacles.
FusionModule2000 Smart Modular Data Center
Maintenance Guide (Fusion Module Actuator) 3 Routine Maintenance
Issue 01 (2020-12-25) Copyright © Huawei Technologies Co., Ltd. 47