The method for setting each alarm is the same. This section describes how to
set Delay of Supply-air HT to 5.
If you need to change alarm settings, log in as the Admin or Engineer user.
NO TICE
Be careful when conguring alarms. Only professional maintenance personnel can
change alarm settings.
Procedure
Step 1 Choose Settings > Alarm Settings > T/H Sensor on the home screen. Figure 4-14
is displayed.
Figure 4-14 Setting alarm parameter 1
Step 2 Tap Delay following Supply-air HT.
Step 3 Set the value to 5 and tap
, as shown in Figure 4-15.
Figure 4-15 Setting alarm parameter 2
----End
NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm Width) 4 ACC Introduction
Issue 17 (2020-10-22) Copyright © Huawei Technologies Co., Ltd. 106