EasyManua.ls Logo

Huawei NetCol5000-A035 - Page 159

Huawei NetCol5000-A035
244 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
NO TE
The normal start pressure of the fan is 2.26 MPa which can be read on the LCD of the
outdoor unit rotational speed controller. You can acquire the pressure reading from the
screen of outdoor unit to get the discharge pressure.
When the outdoor fans are double wind turbines and the outdoor ambient temperature
is below 27°C, one of the fans may not rotate.
Step 8 Adjust the compressor and
humidier input into 0. Exit the diagnostic mode.
Step 9 If high humidity alarm occurs, the following steps are recommended.
1. On the main screen, tap Settings > System Settings > System Control, and
change Heat mode to Dehumid&LT.
2. On the main screen, tap Settings > System Settings > T/H Sensor, and
change T/H control type to Return-air or Cold aisle.
3. Shut down the fresh air system. In modular datacenter, open the modular
doors and ceilings, or open some false panel on the IT rack.
----End
Follow-up Procedure
If you need to adjust the air ow direction, adjust the air deector by performing
the following steps:
1. Remove screws from both sides of the air deector to be adjusted using a
Phillips screwdriver and remove the air
deector, as shown by 1 in Figure 5-8.
2. Remove the upper and lower screws from the air deector using a Phillips
screwdriver, as shown by 2 in Figure 5-8.
3. Put the air
deector upside down and rotate it to the opposite direction of the
slot, as shown by 3 in Figure 5-8.
4. Reinstall the air deector using a Phillips screwdriver.
Figure 5-8 Adjusting the air deector
NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm Width) 5 Power-On Commissioning
Issue 17 (2020-10-22) Copyright © Huawei Technologies Co., Ltd. 149

Table of Contents

Other manuals for Huawei NetCol5000-A035

Related product manuals