EasyManuals Logo

IAI RCP6S User Manual

IAI RCP6S
286 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #88 background imageLoading...
Page #88 background image
3. Operation
Fieldbus Communication
76
RCP6
S
[Basic Operation Procedures]
[1] Operation Mode Setting [Refer to Sections 3.2.1 and 3.8]
Establish the settings for those such as the slave addresses in the Fieldbus using Gateway
Parameter Setting Tool. Establish the settings of the operation mode for all the axes.
1) Establish the setting following the procedure described in Section 3.2.1.
All the connected axes will be in the same operation mode.
2) Setting the gateway parameters to suit the system to be used.
Establish such conducting as the calendar function (clock setting) use or the speed unit
change in Direct Indication Mode.
[2] Parameter Settings [Refer to Sections 3.2.2]
Establish the parameter settings on all the connected axes by using a teaching tool such as
the PC software.
Set the zone (Parameters No.1 and 2) and soft limit (Parameter No.3 and 4) that suit to the
system.
[Refer to Chapter 8 Parameter]
[3] Setting of Position Data [Refer to Sections 3.3]
(Note) Setting of Direct Indication Mode is not necessary.
Set the data for those to be used such as target position, speed, etc. to the position
data.
[4] Fieldbus Settings [Refer to Sections 3.4.1 and 3.4.2]
Assign RCP6S gateway to PLC (master unit).
[Refer to the instruction manuals for the master unit and PLC]
[5] Link to Network
1) Put the operation mode setting switch on the front panel of RCP6S gateway unit to AUTO
side and reboot the power. (By putting to AUTO, Fieldbus line activates.)
2) Once the link to PLC (master unit) is established
(Note 1)
, turn ON MON Signal of the
gateway control signals
(Note 2)
. While MON Signal is ON, control from fieldbus is
available.
Note 1: By referring to 3.9 Fieldbus status LEDs display, confirm that the communication is
established in the normal condition.
Note 2: Refer to 3.4.2 Control Signals of Gateway.
[6] Operation Control in Each Operation Mode [Refer to Sections 3.4.3 to 3.4.8]
1) Send the information of the target position, speed, acceleration/deceleration, etc. from
PLC (master unit) to the RCP6S gateway.
2) The actuator follows the received information of the target position, speed,
acceleration/deceleration, etc. to perform a positioning at the specific coordinates.
3) Confirm the status of positioning complete.
Initial Settin
g
3.1.1
ME0349-4B

Table of Contents

Other manuals for IAI RCP6S

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the IAI RCP6S and is the answer not in the manual?

IAI RCP6S Specifications

General IconGeneral
BrandIAI
ModelRCP6S
CategoryConference System
LanguageEnglish

Related product manuals