Table 1-8. Power specifications for a maximum configuration of the library
Power Specification
Measurement
5U control module 9U expansion module
Voltage 100 to 127
Vac.
200-240 Vac. 100 to 127
Vac.
200-240 Vac.
Frequency 50 to 60 Hz 50 to 60 Hz 50 to 60 Hz 50 to 60 Hz
Current 2.0 A 1.0 A 2.0 A 1.0 A
Inrush current 50 A 100 A 50 A 100 A
Power 200 W 200 W 200 W 200 W
kVA 0.2 0.2 0.2 0.2
kBtu/hr 0.68 0.68 0.68 0.68
Table 1-9. Other specifications for the library
Specification Measurement
Maximum altitude 2500 m (8202 ft) for operating and storage
Table 1-10. Environmental specifications for the library
Environmental
Factor
Operating (see Note) Storage Shipping
Drive temperature
10 to 38°C (50 to
100°F)
10 to 43°C (50 to
109.4°F)
-40 to 60°C (-40 to
140°F)
Heat output 542 W (483 Cal/Hr) Not applicable Not applicable
Relative humidity 20 to 80% 10 to 90% 10 to 90%
Maximum wet bulb
temperature
26°C (79°F) max. 27°C (80.6°F) max. 29°C (84.2°F) max.
Note: The operating environment of the library must not conflict with the media storage
requirements (see “Environmental and Shipping Specifications for Tape Cartridges” on
page 1-14 and the section about media storage requirements in the Setup and Operator
Guide. The library may be capable of operating at elevated temperatures for an extended
period of time, the temperature could shorten the useful life of media that is stored in the
library. If media is stored in the library for more than 10 hours, the storage temperature
requirements for media should be met. It should be assumed that media stored in the
library will be 2 degrees above ambient temperature when the library is powered ON.
Product Environment
The library is designed to operate in a general business environment.
The library meets the acoustical requirements for general business area category
2D. Category 2D states that the library should be installed a minimum of 4 m (13
ft.) from a permanent work station.
To allow for service access, install the library a minimum of 0.9 m (3 ft.) from all
obstacles.
The library is a precision computer peripheral. To ensure maximum longevity of
your library, locate the library away from dust, dirt, and airborne particulates:
1-16 TS3310 Tape Library Setup and Operator Guide