2. Use the IBM Power Configurator utility to ensure current system power consumption is under limitation. For
more information and to download the utility, go to http://www-03.ibm.com/systems/bladecenter/resources/
powerconfig.html.
3. Replace power supply n. (n = power supply number)
80070208-0a02ffff Sensor [SensorElementName] has transitioned to critical from a less severe state. (PS 2 Therm
Fault)
Explanation: This message is for the use case when an implementation has detected a Sensor transitioned to critical
from less severe.
May also be shown as 800702080a02ffff or 0x800702080a02ffff
Severity: Error
Alert Category: Critical - Power
Serviceable: Yes
CIM Information: Prefix: PLAT and ID: 0522
SNMP Trap ID: 4
Automatically notify Support: No
User response:
1. Make sure that there are no obstructions, such as bundled cables, to the airflow from the power-supply fan.
2. Use the IBM Power Configurator utility to ensure current system power consumption is under limitation. For
more information and to download the utility, go to http://www-03.ibm.com/systems/bladecenter/resources/
powerconfig.html.
3. Replace power supply n. (n = power supply number)
8007020c-2502ffff Sensor [SensorElementName] has transitioned to critical from a less severe state. (nvDIMM 02
Status)
Explanation: This message is for the use case when an implementation has detected a Sensor transitioned to critical
from less severe.
May also be shown as 8007020c2502ffff or 0x8007020c2502ffff
Severity: Error
Alert Category: Critical - Other
Serviceable: Yes
CIM Information: Prefix: PLAT and ID: 0522
SNMP Trap ID: 50
Automatically notify Support: No
User response: None