The output frequency of the inverter changes as
the load. And it is mainly used to balance the
power when several inverters drive one load.
Setting range:0.00~10.00Hz
0.00Hz
When the output frequency exceeds the
corresponding frequency of FDT electrical level,
the multi-function digital output terminals will
output the signal of “frequency level detect FDT”
until the output frequency decreases to a value
lower than (FDT electrical level—FDT retention
detection value) the corresponding frequency,
the signal is invalid. Below is the waveform
diagram:
Setting range of P08.32: 0.00Hz~P00.03
(the Max. frequency)
Setting range of P08.33: -100.0~100.0%
(FDT1 electrical level)
50.00