Goodrive200 inverters Function codes
105
Function
code
Name
Detailed instruction of parameters
Default
value
Setting range of P08.34: 0.00 Hz ~P00.03
(the Max. frequency)
Setting range of P08.35: 0.0~100.0%
(FDT2 electrical level)
P08.36
When the output frequency is among the below
or above range of the set frequency, the
multi-function digital output terminal will output
the signal of “frequency arrival”, see the diagram
below for detailed information:
The setting range:0.00Hz~P00.03
(the Max. frequency)
0.00Hz
This parameter is used to control the internal
braking unit.
0:Disable
1:Enable
Note: Only applied to internal braking unit. After
enabling, the overvoltage stall point will increase
by 20V more than the energy braking point.
0 ○
P08.38
After setting the original bus voltage, adjust this
parameter to break the load appropriately. The
factory value changes with voltage level.
The setting range:200.0~2000.0V
In order to prevent customers set the value is too
380V
voltage: