Goodrive200 inverters Function codes
106
Function
code
Name
Detailed instruction of parameters
Default
value
large, it is recommended setting range:
voltage
Set the operation mode of the cooling fan.
0: Normal mode, after the rectifier receives
operation command or the detected temperature
of module is above 45℃ or the module current is
above 20% of the rated current, the fan rotates.
1:The fan keeps on running after power on
(generally for the site with high temperature and
humidity)
0 ○
P08.40
0x00~0x21
LED ones: PWM mode selection
0: PWM mode 1, three-phase modulation and
two-modulation
1: PWM mode 2, three-phase modulation
LED tens: low-speed carrier frequency limit mode
0: Low-speed carrier frequency limit mode 1, the
carrier frequency will limit to 2k if it exceeds 2k at
low speed
1:Low-speed carrier frequency limit mode 2, the
carrier frequency will limit to 4k if it exceeds 4k at
low speed
2: No limit
01
◎
P08.41
Over
commissio
n selection
0x00~0x11
LED ones
0: Invalid
1: Valid
LED tens
0: Light overcommission
0x01
◎