Goodrive200 inverters Function codes
126
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
ation
baud
ratio
upper monitor and the inverter.
0:1200BPS
1:2400BPS
2:4800BPS
3:9600BPS
4:19200BPS
5:38400BPS
6:57600BPS
7:115200BPS
Note: The baud rate between the upper monitor
and the inverter must be the same. Otherwise,
the communication is not applied. The bigger the
baud rate, the quicker the communication
speed.
P14.02
Digital bit
checkout
The data format between the upper monitor and
the inverter must be the same. Otherwise, the
communication is not applied.
1: Even check (E,8,1) for RTU
2: Odd check (O,8,1) for RTU
3:No check (N,8,2) for RTU
4: Even check (E,8,2) for RTU
5: Odd check(O,8,2) for RTU
1
P14.03
A
nswer
delay
0~200ms
It means the interval time between the interval
time when the drive receive the data and sent it
to the upper monitor. If the answer delay is
shorter than the system processing time, then the
answer delay time is the system processing time,
if the answer delay is longer than the system
processing time, then after the system deal with
the data, waits until achieving the answer delay
time to send the data to the upper monitor.
5
P14.04
Fault time 0.0(invalid), 0.1~60.0s 0.0s