Goodrive200 inverters Function codes
131
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
of the
motor
overload
P17.38
PID
output
-100.00~100.00%
0.00%
P17.39
Wrong
download
of
parameter
s
0.00~99.99
0.00
P24 Group Water supply
P24.00
Water
supply
selection
0: Disabled
1: Enabled
0
P24.01
Press
feedback
source
0: AI1 setting value
1: AI2 setting value
2: AI3 setting value
3: HDI setting value
0
P24.02
Hibernatio
n check
0: Hibernate as the setting frequencyP24.03
1: Hibernate as the feedback pressureP24.04
0
P24.03
Starting
frequency
of the
hibernation
0.00~P0.03(the Max. frequency)
10.00
Hz
P24.04
Starting
pressure of
hibernation
0.00~100.0% 50.0%
P24.05
Hibernatio
n delay
time
0.0~3600.0s 5.0s
P24.06
Hibernatio
n awake
0: Awake as the setting frequencyP24.07
1: Awake as the feedback pressureP24.08
0