Goodrive200 inverters Basic operation instruction
141
Function
code
Name Detailed instruction of parameters
Default
value
5:Multi-step setting upper-limit frequency
6:MODBUS communication setting
upper-limit frequency
7~9: Reserved
P03.16
Keypad setting for upper
frequency of forward
rotation
Setting range:0.00Hz~P00.03
(the Maximum frequency)
50.00Hz
P03.17
Keypad setting for upper
frequency of reverse
rotation
50.00Hz
P03.18
Upper electromotion
torque
source
0:Keypad setting upper-limit
frequency(P03.20 sets P03.18, P03.21
sets P03.19)
1: AI1
2: AI2
3: AI3
4: HDI
5:MODBUS communication
6~8: Reserved
0
P03.19
Upper braking torque
source
0
P03.20
Keypad setting of
electromotion torque
0.0~300.0%(rated current of the motor)
180.0%
P03.21
Keypad setting of braking
torque
180.0%
P03.22
Weakening coefficient in
constant power zone
0.1~2.0 0.3
P03.23
Lowest
weakening point in
constant power zone
10%~100% 20%
P03.24 Max. voltage limit 0.0~120.0% 100.0%
P03.25 Pre-exciting time 0.000~10.000s 0.300s
P17.32 Magnetic flux linkage 0.0~200.0% 0