Goodrive200 inverters Basic operation instruction
147
Function
code
Name Detailed instruction of parameters
Default
value
P00.00
Speed control
mode
1: SVC
2: SVPWM control (applying to AM)
2
P03.11
Torque setting
method
0:Torque control is invalid
1:Keypad setting torque(P03.12)
2:Analog AI1 setting torque
3:Analog AI2 setting torque
4:Analog AI3 setting torque
5:Pulse frequency HDI setting torque
6:Multi-step torque setting
7:MODBUS communication setting torque
8~10:Reserved
0
P03.12
Keypad setting
torque
-300.0%~300.0%
( the rated current of the motor)
50.0%
P03.13
Torque reference
filter time
0.000~10.000s 0.010s
P03.14
Upper frequency of
forward rotation in
vector control
0:Keypad (P03.16 sets P03.14,P03.17 sets
P03.15)
1: AI1
2: AI2
0
P03.15
Upper frequency of 0