Goodrive200 inverters Basic operation instruction
154
Function
code
Name Detailed instruction of parameters
Default
value
P01.03
The braking current before
starting
0.0~100.0% 0.0%
P01.04
The braking time before
starting
0.00~50.00s 0.00s
P01.05 ACC/DEC selection
0:Linear type
1:Reserved
0
P01.08 Stop mode
0:Decelerate to stop
1:Coast to stop
0
P01.09
Starting frequency of DC
braking
0.00Hz~P00.03(the Max. frequency) 0.00Hz
P01.10
Waiting time before DC
braking
0.00~50.00s 0.00s
P01.11 DC braking current 0.0~150.0% 0.0%
P01.12 DC braking time 0.00~50.00s 0.00s
P01.13
Dead time of FWD/REV
rotation
0.0~3600.0s 0.0s
P01.14
Shifting between
FWD/REV rotation
0:Switch after 0 frequency
1:Switch after the starting frequency
2:Switch after the stopping speed
0
P01.15 Stopping speed 0.00~100.00Hz 0.50 Hz
P01.19
Action selection
(operation
frequency<lower
frequency limit and valid
when the lower limit >0)
0: Run at the lower-limit frequency
1: Stop
2: Hibernation
0
P01.20
Hibernation restore delay
time
0.0~3600.0s(valid when P01.15=2) 0.0s
P01.21 Restart after power off
0: Disable
1: Enable
0
P01.22
The waiting time of restart
after power off
0.0~3600.0s(valid when P01.21=1) 1.0s