Goodrive200 inverters Basic operation instruction
155
Function
code
Name Detailed instruction of parameters
Default
value
P01.23 Start delay time 0.0~60.0s 0.0s
P01.24
Delay time of the stop
speed
0.0~10.0 s 0.0s
P05.01~P0
5.09
Digital input function
selection
1: Forward rotation operation
2: Reverse rotation operation
4: Forward rotation jogging
5: Reverse rotation jogging
6: Coast to stop
7: Fault reset
8: Operation pause
21:ACC/DEC time option1
22:ACC/DEC time option2
30:ACC/DEC prohibition
P08.06 Jogging frequency 0.00~P00.03(the Max. frequency) 5.00Hz
P08.07 Jogging ACC time 0.0~3600.0s
Depend
on model
P08.08 Jogging DEC time 0.0~3600.0s
Depend
on model
P08.00 ACC time 2 0.0~3600.0s
Depend
on model
P08.01 DEC time 2 0.0~3600.0s
Depend
on model
P08.02 ACC time 3 0.0~3600.0s
Depend
on model
P08.03 DEC time 3 0.0~3600.0s
Depend
on model
P08.04 ACC time 4 0.0~3600.0s
Depend
on model
P08.05 DEC time 4 0.0~3600.0s
Depend
on model
P08.28 Fault reset times 0~10 0