EasyManuals Logo

INVT GD200-037G/045P-4 User Manual

INVT GD200-037G/045P-4
266 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #160 background imageLoading...
Page #160 background image
Goodrive200 inverters Basic operation instruction
159
Function
code
Name
Detailed instruction of parameters Default
value
P00.05
Lower limit of the running
frequency
0.00Hz~P00.04 0.00Hz
P00.06 A frequency command
0:Keypad data setting
1:Analog AI1 setting
2:Analog AI2 setting
3:Analog AI3 setting
4:High-speed pulse HDI setting
5:Simple PLC program setting
6: Multi-step speed running setting
7: PID control setting
8:MODBUS communication setting
9~11:Reserved
0
P00.07 B frequency command
0:Keypad data setting
1:Analog AI1 setting
2:Analog AI2 setting
3:Analog AI3 setting
4:High-speed pulse HDI setting
5:Simple PLC program setting
6: Multi-step speed running setting
7: PID control setting
8: MODBUS communication setting
9~11: Reserved
2
P00.08
B frequency command
reference
0: The Max. output frequency
1: A frequency command
0
P00.09
Combination of the setting
source
0:A
1:B
2:(A+B)combination
3:(A-B)combination
4:Max(A,B)combination
5:Min(A,B)combination
0
P05.01~P0
5.09
Multi-function digital input
terminals
10:Increasing frequency setting(UP)
11:Decreasing frequency

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the INVT GD200-037G/045P-4 and is the answer not in the manual?

INVT GD200-037G/045P-4 Specifications

General IconGeneral
BrandINVT
ModelGD200-037G/045P-4
CategoryInverter
LanguageEnglish

Related product manuals