Page #166 background image
Goodrive200 inverters Basic operation instruction
165
Set value
Function Instructions
9 Output torque 0~2 times of the rated current of the motor
10 AI1 0~10V/0~20mA
11 AI2 0~10V/0~20mA
12 AI3 -10V~10V
13 HDI 0.00~50.00kHz
14
MODBUS communication set
value 1
-1000~1000,1000 corresponds to 100.0%
15
MODBUS communication set
value 2
-1000~1000,1000 corresponds to 100.0%
16~21 Reserved
22
Torque current (the rated
current of the motor)
0~2 times of the rated current of the motor
23
Ramp reference
frequency(with sign)
0~ the Max. output frequency
24~30 Reserved
Relative parameters list:
Function
code
Name
Detailed instruction of parameters Default
value
P06.00 HDO output
0:Open collector pole high speed pulse
output
1: Open collector pole output
0
P06.14 AO1 output
0:Running frequency
1:Set frequency
2:Ramp reference frequency
3:Running rotation speed
4:Output current (relative to the rated
current of the inverter)
5:Output current(relative to the rated
current of the motor)
6:Output voltage
7:Output power
8:Set torque value
0
P06.15 AO2 output
0
P06.16
HDO high-speed pulse
output selection
0