Goodrive200 inverters Fault tracking
203
F
ault code
Fault type Possible cause What to do
CE
Communication
error
The baud rate setting is
incorrect
Fault occurs to the
communication wiring.
The communication
address is wrong
There is strong
interference to the
communication
Set proper baud rate
Check the communication
connection distribution
Set proper communication
address
Chang or replace the
connection distribution or
improve the
anti-interference capability
ItE
Current detection
fault
The connection of the
control board is not good
Hoare components is
broken
The modifying circuit is
abnormal
Check the connector and
repatch
Change the hoare
Change the main control
panel
tE Autotuning fault
The motor capacity does
not comply with the
inverter capability
The rated parameter of the
motor does not set
correctly.
The offset between the
parameters autotunting
and the standard
parameter is huge
Autotune overtime
Change the inverter mode
Set the rated parameter
according to the motor
name plate
Empty the motor load and
reindentify
Check the motor
connection and set the
parameter.
Check if the upper limit
frequency is above 2/3 of
the rated frequency.
EEP EEPROM fault
Error of controlling the
write and read of the
parameters
Damage to EEPROM
Press STOP/RST to reset
Change the main control
panel