Fault type Possible cause What to do
STo
Maladjustment
fault
The control parameters of
the synchronous motors
not set properly
The autoturn parameter is
not right
The inverter is not
connected to the motor
Check the load and
ensure it is normal
Check whether the control
parameter is set properly
or not
Increase the
maladjustment detection
time
END
Time reach of
factory setting
The actual running time of
the inverter is above the
internal setting running
time
Ask for the supplier and
adjust the setting running
time
PCE
Keypad
communication
fault
The connection of the
keypad wires is not good
or broken
The keypad wire is too
long and affected by
strong interference
There is circuit fault on the
communication of the
keypad and main board
Check the keypad wires
and ensure whether there
is mistake
Check the environment
and avoid the interference
source
Change the hardware and
ask for service
DNE
Parameters
downloading fault