Goodrive200 inverters Function codes
53
Function
code
Name
Detailed instruction of parameters
Default
value
0:Invalid
1:Valid during the whole procedure
The auto-adjusting function of the inverter can
cancel the impact on the output voltage of the
inverter because of the bus voltage fluctuation.
0:G type, for the constant torque load of rated
parameters
1:P type; for the variable torque load of rated
parameters (fans and water pumps)
GD200 series inverters can use G/P type, the
available motor power of G type is small one
power file than that of P type.
0 ◎
P00.18
0:No operation
1:Restore the default value
2:Clear fault records
Note: The function code will restore to 0 after
finishing the operation of the selected function
code.
Restoring to the default value will cancel the user
password, please use this function with caution.
0 ◎
P01 Group Start-up and stop control
P01.00
0:Start-up directly:start from the starting
frequency P01.01
1:Start-up after DC braking: start the motor from
the starting frequency after DC braking (set the
parameter P01.03 and P01.04). It is suitable in
the cases where reverse rotation may occur to
the low inertia load during starting.
2: Start-up after speed tracking: start the rotating
motor smoothly after tracking the rotation speed
and direction automatically. It is suitable in the
0 ◎