Goodrive200 inverters Function codes
54
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
cases where reverse rotation may occur to the
big inertia load during starting.
Note: This function is available for the inverters of
4kW and above.
P01.01
Starting
frequency
of direct
start
Starting frequency of direct start-up means the
original frequency during the inverter starting.
See P01.02 for detailed information.
Setting range: 0.00~50.00Hz
0.50Hz
P01.02
Retention
time of the
starting
frequency
Set a proper starting frequency to increase the
torque of the inverter during starting. During the
retention time of the starting frequency, the
output frequency of the inverter is the starting
frequency. And then, the inverter will run from the
starting frequency to the set frequency. If the set
frequency is lower than the starting frequency,
the inverter will stop running and keep in the
stand-by state. The starting frequency is not
limited in the lower limit frequency.
Setting range: 0.0~50.0s
0.0s
P01.03
The
braking
current
before
The inverter will carry out DC braking at the
braking current set before starting and it will
speed up after the DC braking time. If the DC
braking time is set to 0, the DC braking is invalid.
0.0%