Goodrive200 inverters Function codes
62
Function
code
Name
Detailed instruction of parameters
Default
value
0: No protection
1: Common motor (with low speed
compensation). Because the heat-releasing
effect of the common motors will be weakened,
the corresponding electric heat protection will be
adjusted properly. The low speed compensation
characteristic mentioned here means reducing
the threshold of the overload protection of the
motor whose running frequency is below 30Hz.
2: Variable frequency motor (without low speed
compensation) Because the heat-releasing effect
of the specific motors won’t be impacted by the
rotation speed, it is not necessary to adjust the
protection value during low-speed running.
2 ◎
P02.27
Motor 1
over load
protection
Times of motor overload M = Iout/(In*K)
In is the rated current of the motor, Iout is the
output current of the inverter and K is the motor
protection coefficient.
So, the bigger the value of K is, the smaller the
value of M is. When M =116%, the fault will be
reported after 1 hour, when M =200%, the fault
will be reported after 1 minute, when M>=400%,
the fault will be reported instantly.
Setting range: 20.0%~120.0%
100.0%
coefficient
Correct the power displaying of motor 1.
Only impact the displaying value other than the