Goodrive200 inverters Function codes
73
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
setting
voltage
when the voltage setting channel is selected as
“keypad selection”
The setting range:0.0%~100.0%
P04.29
Voltage
increasing
time
Voltage increasing time is the time when the
inverter accelerates from the output minimum
voltage to the output maximum voltage.
Voltage decreasing time is the time when the
inverter decelerates from the output maximum
voltage to the output minimum voltage.
The setting range:0.0~3600.0s
5.0s
P04.30
Voltage
decreasing
time
5.0s
P04.31
Maximum
output
voltage
Set the upper and low limit of the output voltage.
The setting range of P04.31:P04.32~100.0%
(the rated voltage of the motor)
The setting range of P04.32:0.0%~ P04.31
(the rated voltage of the motor)
100.0%
P04.32
Minimum
output
voltage
0.0%
P04.33
Weaking
coefficient
at constant
power
Used to adjust the output voltage of inverter in
SVPWM mode when weaking magnetic.
Note: Invalid in constant-torque mode.
The setting range of P04.33: 1.00~1.30
1.00
P04.34
Reserved