Goodrive270 series VFD for fan and pump Function parameter list
-149-
Name Description Default
P04.14
Torque boost of
Refer to the descriptions for P04.01 and
.
setting range: 0.0%: Automatic; 0.1%±
setting range: 0.0%±50.0% (of the rated
0.0% ƻ
P04.15
Torque boost cut-
of motor 2
20.0% ƻ
P04.16
V/F frequency point
1 of motor 2
Refer to the descriptions for P04.03 and
8.
setting range: 0.00Hz±P04.18
setting range: 0.0%±
110.0% (of the rated
voltage of motor 2)
setting range: P04.16±P04.20
setting range: 0.0%±
110.0% (of the rated
voltage of motor 2)
setting range: P04.18±P12.02 (Rated
P04.18±P12.16 (Rated
setting range: 0.0%±
110.0% (of the rated
voltage of motor 2)
0.00Hz ƻ
P04.17
V/F voltage point 1
00.0% ƻ
P04.18
V/F frequency point
2 of motor 2
0.00Hz ƻ
P04.19
V/F voltage point 2
00.0% ƻ
P04.20
V/F frequency point
3 of motor 2
0.00Hz ƻ
P04.21
V/F voltage point 3
of motor 2
00.0% ƻ
P04.22
V/F slip
compensation gain
of motor 2
Used to compensate for the motor rotating speed
change caused by load change in the space
voltage vector mode, and thus improve the
rigidity of the mechanical characteristics of the
motor. You need to calculate the rated slip
frequency of the motor as foll
ows:
f=f
b
-n*p/60
b
is the rated frequency of the motor 2,
corresponding to function code
P12.02. n is the
rated rotating speed of the motor 2,
corresponding to function code
P12.03. p is the
of pole pairs of the motor. 100.0%
corresponds to the rated slip frequency
ᶭ f of
Setting range: 0.0±200.0%
0.0% ƻ
P04.23
Low-frequency
oscillation control
In space voltage vector control mode, the motor,
especially the large
-power motor, may
experience current oscillation at certain
frequencies, which may cause unstable motor
10 ƻ