Goodrive270 series VFD for fan and pump Function parameter list
-169-
Name Description Default
Bit 3: Output terminal state
Bit 4: PID reference value (% on)
Bit 5: PID feedback value (% on)
-speed pulse HDIA frequency
t 12: Pulse count value
Bit 13: PLC and current step number of
multi
-step speed
Bit 14: Upper limit frequency (HZ on)
P07.08
Frequency display
±10.00
Display frequency = Running frequency * P07.08
1.00 ƻ
P07.09
Rotational speed
display coefficient
±999.9%
Mechanical rotation speed = 120 * (Displayed
running frequency) * P07.09/(Motor pole pairs)
100.0% ƻ
P07.10
coefficient
±999.9%
Linear speed=(Mechanical rotation speed) *
P07.10
1.0% ƻ
P07.11
Rectifier bridge
20.0±120.0°C ƽ
ƽ
P07.13
Control board
±655.35 ƽ
P07.14
Local accumulative
running time
±65535h ƽ
P07.15
VFD electricity
VFD electricity consumption.
onsumption = P07.15*1000 +
setting range: 0±65535 kWh (*1000)
P07.16 setting range: 0.0±999.9 kWh
ƽ
P07.16
VFD electricity
consumption LSB
ƽ
P07.18 VFD rated power
±3000.0kW
Model
ƽ