Goodrive270 series VFD for fan and pump Function parameter list
-191-
Name Description Default
P11.05 Current limit mode
During accelerated running, as the load is too
large, the actual acceleration rate of motor is
lower than that of output frequency, if no
measures are taken, t
he VFD may trip due to
overcurrent during acceleration.
±0x11
Ones place: Current limit action selection
Tens: Hardware current limit overload alarm
selection
01 Ƽ
P11.06
Automatic current
limit threshold
-limit protection function detects output
current during running, and compares it with the
current
-limit level defined by P11.06
, if it exceeds
the current
-limit level, the VFD will run at stable
frequency during accelerat
ed running, or run in
decreased frequency during constant
-speed
running; if it exceeds the current
-limit level
continuously, the VFD output frequency will drop
continuously until reaching lower limit frequency.
When the output current is detected to be low
er
-limit level again, it will continue
Output current A
Output frequency f
Current-limit
threshold
Set
frequency
Acceleration
Constant
speed
Time t
Time t
setting range: 50.0±180.0%
P11.07 setting range: 0.00±50.00Hz/s
120.0% Ƽ
P11.07
Frequency
during current limit
10.00
Hz/s
Ƽ
P11.08
VFD/motor OL/UL
pre-alarm selection
±0x1132
0: Motor OL/UL pre-alarm, relative to motor rated
0x000 ƻ