Goodrive270 series VFD for fan and pump Function parameter list
-192-
Function
code
Name Description Default
Modify
current.
1: VFD OL/UL pre
-alarm, relative to the VFD
rated current
2: Motor output torque ov
erload/underload
pre
-alarm, relative to rated motor torque.
Tens place:
0: The VFD continues to work for an OL/UL
alarm.
1: The VFD continues to work for a UL alarm but
stops running for an OL fault.
2: The VFD continues to work for an OL alarm
but stops r
unning for a UL fault.
3. The VFD stops running for an OL/UL alarm.
Hundreds place:
0: Detect all the time.
1: Detect during constant speed running.
Thousands place: VFD overload current
reference selection
0: Related to current calibration coefficient
1: Irrelated to current calibration coefficient
P11.09
Overload pre-
alarm
detection level
If the VFD or motor output current is larger than
the overload pre
-alarm detection level (P11.09),
and the duration exceeds the overlo
ad pre-
alarm
detection time (
P11.10), overload pre-alarm
signal will be outputted.
Y,
RO1, RO2
Output current
Overload pre-alarm
threshold
Time t
Time t
Pre-alarm time tPre-alarm time t
P11.09
setting range: P11.11±200%
P11.10 setting range: 0.1±3600.0s
Type G:
150%
Type F:
120%
ƻ
P11.10
Overload pre-
alarm
detection time
1.0s ƻ