Goodrive270 series VFD for fan and pump Function parameter list
-208-
Name Description Default
P17.05
t motor speed.
0 RPM ƽ
P17.06 Torque current
Displays the present torque current of the VFD.
0.0A ƽ
P17.07 Exciting current
Displays the present exciting current of the VFD.
Range: -3000.0±3000.0A
0.0A ƽ
P17.08 Motor power
Displays the present motor power; 100% relative
to the rated motor power. The positive value is
the motoring state while the negative value is the
generating state.
-300.0±300.0% (relative to the rated
0.0% ƽ
P17.09
Output torque
percentage
Displays the present output torque of the VFD;
100% relative to the rated motor torque. During
forward running, the positive value is the
motoring state while the negative value is
generating state. During reverse running, the
positive val
ue is the generating state while the
negative value is the motoring state.
0.0% ƽ
P17.10
Estimated motor
frequency
Displays the estimated motor rotor frequency
under the open
-loop vector condition.
0.00Hz ƽ
P17.11 DC bus voltage
Displays the present DC bus voltage of the VFD.
Range: 0.0±2000.0V
0V ƽ
P17.12
status
Displays the present digital input terminal state of
the VFD.
±03F
Corresponds to HDIA, S4, S3, S2 and S1
respectively.
0 ƽ
P17.13
Digital output
terminal status
Displays the present digital output ter
minal state
±000F
RO2, RO1, HDO and Y1
0 ƽ
P17.14
Digital adjustment
value
Displays the adjustment on the VFD through the
UP/DOWN
terminal.
0.00Hz ƽ