Goodrive270 series VFD for fan and pump Basic operation guidelines
-45-
The running command channel can be set by terminal commands besides P00.01 and P00.02.
Channel of
running
commands
(P00.01)
Multifunction
terminal function 36
(Switch the running
command channel
Multifunction
terminal function 37
(Switch the running
command channel
Multifunction
terminal function 38
(Switch the running
command channel
Keypad / Terminal Communication
Terminal Keypad / Communication
Communication Keypad Terminal /
Note: "/" indicates this multifunction terminal is invalid under present reference channel.
Related parameter list:
Name Description Default
P00.00 Speed control mode
0: Sensorless vector control (SVC) mode 0
1: Sensorless vector control (SVC) mode 1
2: Space voltage vector control mode
Note: Before using a vector control mode (0 or
1), enable the VFD to perform motor parameter
2
P00.01
Channel of running
commands
0: Keypad
1: Terminal
0
P00.02
Communication
mode of running
commands
0: Modbus
1: PROFIBUS/CANopen/DeviceNet
2: Ethernet
3: EtherCAT/PROFINET
4: Programmable expansion card
5: Wireless communication card
0
P00.15
Motor parameter
autotuning
0: No operation
1: Rotary autotuning 1.
Comprehensive motor parameter autotuning. It is
recommended to use rotating autotuning when high
control accuracy is required.
2: Static autotuning 1 (comprehensive autotuning);
static autotuning 1 is used in cases where the motor
cannot be disconnected from load.
3: Static autotuning 2 (partial autotuning); when the
0