Goodrive270 series VFD for fan and pump Basic operation guidelines
-46-
Function
code
Name Description Default
present motor is motor 1, only P02.06, P02.07, and
P02.08 are autotuned; when the present motor is
motor 2, only P12.06, P12.07, and P12.08 are
autotuned.
4: Rotary autotuning 2, which is similar to rotary
autotuning 1 but only valid for AMs.
5: Static autotuning 3 (partial autotuning), which is
valid only for AMs.
P00.18
Function parameter
restore
0: No operation
1: Restore default values
2: Clear fault records
Note: After the selected operation is performed, the
function code is automatically restored to 0.
Restoring the default values may delete the user
password. Exercise caution when using this
function.
0
P02.00 Type of motor 1
0: Asynchronous motor (AM)
1: Synchronous motor (SM)
0
P02.01
Rated power of AM
1
0.1±3000.0kW
Model
depended
P02.02
Rated frequency of
AM 1
0.01Hz±P00.03(Max. output frequency) 50.00Hz
P02.03
Rated speed of AM
1
1±60000rpm
Model
depended
P02.04
Rated voltage of AM
1
0±1200V
Model
depended
P02.05
Rated current of AM
1
0.8±6000.0A
Model
depended
P02.15
Rated power of SM
1
0.1±3000.0kW
Model
depended
P02.16
Rated frequency of
SM 1
0.01Hz±P00.03(Max. output frequency) 50.00Hz
P02.17
Number of pole pairs
of SM 1
1±50 2
P02.18
Rated voltage of SM
1
0±1200V
Model
depended
P02.19
Rated current of SM
1
0.8±6000.0A
Model
depended

Table of Contents