Goodrive270 series VFD for fan and pump Basic operation guidelines
-61-
Name Description Default
function code.
P04.40
Enabling IF mode for
0: Disable
0
P04.41
Current setting in IF
mode for AM 1
When IF control is adopted for AM 1, the function
code is used to set the output current. The value is
a percentage in relative to the rated current of the
motor.
Setting range: 0.0±200.0%
120.0%
P04.42
Proportional
coefficient in IF mode
for AM 1
When IF control is adopted for AM 1, the function
code is used to set the proportional coefficient of
the output current closed-loop control.
350
P04.43
Integral coefficient in
IF mode for AM 1
When IF control is adopted for AM 1, the function
code is used to set the integral coefficient of the
output current closed-loop control.
150
P04.44
Starting frequency
point for switching off
0.00±P04.50 10.00Hz
P04.45
Enabling IF mode for
0: Disable
0
P04.46
Current setting in IF
mode for AM 2
When IF control is adopted for AM 2, the function
code is used to set the output current. The value is
a percentage in relative to the rated current of the
motor.
Setting range: 0.0±200.0%
120.0%
P04.47
Proportional
coefficient in IF mod
for AM 2
When IF control is adopted for AM 2, the function
code is used to set the proportional coefficient of
output current closed-loop control. Setting range:
350
P04.48
Integral coefficient in
IF mode for AM 2
When IF control is adopted for AM 2, the function
code is used to set the integral coefficient of output
current closed-loop control. Setting range: 0±5000
150
P04.49
Starting frequency
point for switching off
0.00±P04.51 10.00Hz