Goodrive270 series VFD for fan and pump Basic operation guidelines
-83-
0
1
2
3
.
.
.
.
.
.
19
20
P06.14
P06.16
AO1
HDO
P06.21
P06.17
P06.18
P06.19
P06.20
P06.27
P06.28
P06.29
P06.30
P06.31
P06.00
(HDO output type)
0
1
P06.00
0: Open collector high-
speed pulse output
1: Open-collector output
Analog output curve setting
Analog output selection
Analog output filter
P06.15
(Default value: 0)
P06.22
P06.23
P06.24
P06.25
P06.26 AO0
(Default value: 0)
(Default value: 0)
AO output relationship description:
(The min. value and max. value of the output correspond to 0.% and 100.00% of the pulse or analog
default output. The actual output voltage or pulse frequency corresponds to the actual percentage,
which can be set through function codes.)
Setting
Function
Description
0
Running frequency
0±Max. output frequency
1
Set frequency
0±Max. output frequency
2
Ramp reference frequency
0±Max. output frequency
3 Rotational speed
0±Synchronous speed corresponding to
max. output frequency
4
Output current (relative to the VFD)
0±Twice the VFD rated current
5
Output current (relative to motor)
0±Twice the motor rated current
6
Output voltage
0±1.5 times the VFD rated voltage
7
Output power
0±Twice the motor rated power
8 Set torque value (bipolar)
0±Twice the motor rated current. A negative
value corresponds to 0.0% by default.
9
Output torque (absolute value)
0±±(Twice the motor rated torque)
10
AI1 input
0±10V/0±20mA
11 AI2 input
0V±10V. A negative value corresponds to
0.0% by default.
12
AI3 input
0±10V/0±20mA
13
High-speed pulse HDIA input
0.00±50.00kHz
14
Value 1 set through Modbus
communication
0±1000
15
Value 2 set through Modbus
communication
0±1000