Goodrive30 Series VFD Function parameter list
-43-
FWD/REV
running
switching
mode
The function code is used to set the switching
threshold of the VFD.
0: Switch at zero frequency
1: Switch at the starting frequency
2: Switch after the speed reaches the stop speed
with a delay
Stop speed
detection
mode
0: Detect by the set speed (without stop delay)
1: Detect by the feedback speed (only valid for
vector control)
Feedback
speed
detection
time
When P01.16=1, the feedback frequency of the
VFD is less than or equal to P01.15 and is
detected during the time set by P01.17, the VFD
will stop; otherwise, the VFD stops in the time set
by P01.17.
Time t
Stop speed
A
Ramp reference
frequency
Output frequency
Frequency f
P01.24 P01.17
B
C
Running A
Running B
Running C
Setting range: 0.00–100.00s (only valid when
P01.16=1)
Terminal-ba
sed running
command
protection
at power-on
When the channel of running commands is
terminal control, the system detects the state of
the running terminal during power-on.
0: The terminal running command is invalid at
power-on. Even the running command is
considered as valid during power-on, the VFD
does not run and it keeps the protection state
until the running command is canceled and
enabled again.
1: The terminal running command is valid at
power-on. If the running command is considered
as valid during power-on, the VFD is started
automatically after the initialization.
Note: Exercise caution before using this