Goodrive30 Series VFD Function parameter list
-78-
Function
code
Name
Description
Default
Modify
P07.16
Low bit of
power
consumptio
n of the
VFD
P07.17
Reserved
Reserved
P07.18
Rated VFD
power
0.43000.0kW
P07.19
Rated VFD
voltage
501200V
P07.20
Rated VFD
current
0.16000.0A
P07.21
Factory bar
code 1
0x00000xFFFF
P07.22
Factory bar
code 2
0x00000xFFFF
P07.23
Factory bar
code 3
0x00000xFFFF
P07.24
Factory bar
code 4
0x00000xFFFF
P07.25
Factory bar
code 5
0x00000xFFFF
P07.26
Factory bar
code 6
0x00000xFFFF
P07.27
Present
fault type
0: No fault
1: Inverter unit U phase protection (OUt1)
2: Inverter unit V phase protection (OUt2)
3: Inverter unit W phase protection (OUt3)
4: Overcurrent during acceleration (OC1)
5: Overcurrent during deceleration (OC2)
6: Overcurrent during constant speed running
(OC3)
7: Overvoltage during acceleration (OV1)
8: Overvoltage during deceleration (OV2)
9: Overvoltage during constant speed running
(OV3)
10: Bus undervoltage (UV)
11: Motor overload (OL1)
P07.28
Last fault
type
P07.29
2nd-last
fault type
P07.30
3rd-last
fault type
P07.31
4th-last fault
type
P07.32
5th-last fault
type

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the INVT Goodrive30 VFD Series and is the answer not in the manual?

INVT Goodrive30 VFD Series Specifications

General IconGeneral
BrandINVT
ModelGoodrive30 VFD Series
CategoryInverter
LanguageEnglish

Related product manuals