EasyManuals Logo
Home>Johnson Controls>Controller>FMS-2000C

Johnson Controls FMS-2000C User Manual

Johnson Controls FMS-2000C
62 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #40 background imageLoading...
Page #40 background image
FMS-2000C
LIT-12013504
40
Specifying the K-factor for CO
2
1. On the home screen, tap the Settings icon to enter the Settings menu.
2. To view analog input settings, tap Analog I/O.
3. To nd the analog input you want to adjust, swipe left.
4. On the ANALOG screen, tap K-Factor.
5. Enter the K-Factor that the manufacturer provided with the sensor.
6. To conrm the settings, tap the Checkmark icon.
Enabling the alarm and changing the alarm limits for CO
2
1. On the home screen, tap the Settings icon.
2. On the SETTINGS screen, tap Analog I/O.
3. To nd the analog input you want to set up the alarm for, swipe left.
4. Scroll down and tap the Alarm Setup arrow.
5. Switch Alarm Enabled on.
6. Tap the High Alarm Setpoint arrow.
7. Enter the High Alarm Setpoint and tap the Checkmark to conrm your settings.
8. Tap the High Warning Limit arrow.
9. Enter the High Warning Limit and tap the Checkmark to conrm your settings.
10. Tap the Low Warning Limit arrow.
11. Enter the Low Warning Limit and tap the Checkmark to conrm your settings.
Naming the CO
2
input
Set up a name for the analog input you want to appear on the home screen. If your FMS-2000C controller is in portrait mode, you can
have up to 16 characters. If your FMS-2000C controller is in landscape mode, you can have 12 characters.
1. On the home screen, tap the Settings icon to enter the Settings menu.
2. To view analog input settings, tap Analog I/O.
3. To nd the analog input you want to set up a new name for, swipe left.
4. On the ANALOG screen, scroll down and tap the Name arrow.
5. On the Name screen enter a new name.
6. To conrm the new name, tap the Checkmark icon.
Conguring the analog output for CO
2
control
If you are controlling CO
2
, congure the analog input to the corresponding analog output as required by the specic application. Refer to
the submittal package wiring diagrams to map the analog output correctly.
Changing the operating mode for CO
2
control
Each of the four analog outputs of the FMS-2000C controller can be congured for the following operating modes:
Direct operating mode
PID operating mode
In direct operating mode, the output tracks the mapped analog input directly or inversely. The PID operating mode may or may not
employ the proportional-integral-derivative scheme for closed-loop control of the analog output. The range of the output can or cannot
include an o󰀨set. This is independent of the mode the analog output is congured to.
To change the operating mode, complete the following steps:
1. On the home screen, tap the Settings icon to enter the Settings menu.
2. To view analog input settings, tap Analog I/O.
3. To nd the analog output you want to change the operating mode for, swipe left.
4. On the ANALOG screen, tap Output.
5. To change the operating mode, expand Operating Mode arrow and tap Direct Analog or PID Analog.
6. Collapse Operating Mode to save the new settings.
Setting the signal range for CO
2
control
1. On the home screen, tap the Settings icon to enter the Settings menu.
2. To view analog input settings, tap Analog I/O.
3. To nd the analog output you want to adjust, swipe left.
4. On the ANALOG screen, tap Output.
5. On the Output screen, expand Range and choose from the following:
0-5V, 0-10V, 0-20mA
1-5V, 2-10V, 4-20mA
6. To save the new settings, collapse Range.

Table of Contents

Other manuals for Johnson Controls FMS-2000C

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls FMS-2000C and is the answer not in the manual?

Johnson Controls FMS-2000C Specifications

General IconGeneral
BrandJohnson Controls
ModelFMS-2000C
CategoryController
LanguageEnglish

Related product manuals