Configuration and Programming
February 2012 3-34 P/N 06-237058-001
FOOTNOTES (Figure 3-27):
34 Global Acknowledge. Activate Global Acknowledge. Purpose: To enable the "Acknowledge"
Switch to process any combination of up to 30 unacknowledged supervisory or trouble events.
35 Global Acknowledge of Alarms. Configure the Global Alarm Acknowledge. Purpose: When
this feature is enabled, when the operator presses the “Acknowledge” key, all current alarms are
acknowledged. If this feature is disabled, the operator must acknowledge each alarm individually.
36 Alarm Verify. Change the Smoke-Detectors’ Alarm-Verification-Delay Period. Purpose: To
change the period of time that the ARIES NETLink control unit will wait for a second, confirming
signal from a smoke detector (or any other alarm-initiating device) that an alarm condition is
valid and actually exists. The alarm verification period is programmable from 30 to 180 seconds
in one-second increments, or 0 (zero).
37 PAS. Change the Smoke-Detectors’ Positive-Alarm Sequence Investigation Period. Purpose:
To change the period of time that the ARIES NETLink control unit will wait for the occupants to
investigate a smoke-detector’s positive-alarm-sequence report before it executes the smoke-
detector's programmed alarm actions. The operator must reset the control unit before this time
period expires or the programmed alarm actions will occur.
38 Nightly Test Time. Purpose: To set the time, once per night, when the panel performs a SLC
device test.
39 Deregister Module. Purpose: To remove a module from the backplane configuration.
40 Learn Backplane. Purpose: To add any modules not yet in the configuration but installed in the
backplane to the configuration, with default settings.