Configuration and Programming
February 2012 3-50 P/N 06-237058-001
8 RRM Group. Activate or De-Activate Remote Release Modules.
Purpose: To manually activate or de-activate one or more remote release modules during system
testing to confirm the proper operation.
Note: All remote release modules must be manually de-activated via a menu operation or a system
reset before the system can be returned to normal operating condition.
CAUTION
There is no indication at the control unit that an output is activated. Be sure to de-activate
the output after proper operation has been confirmed.
Ensure that the remote release modules are not activating suppression systems.
Physically disconnect the wiring to all agent-release and pre-action-sprinkler circuits if
the control modules are activating suppression systems. Restore the system to normal
operating condition at the conclusion of all RRM activations and any other functional
tests.