KurzB‐SeriesOperationsGuide 3–5
Program ModeBasic Access
Basic Flow Meter Setup
BasicflowmetersetupisconfiguredinProgrammode,whichyouaccessbypressingPandusing
theBasicaccesscode.AlloftheparametersavailableinBasicSetupareavailableinasindividual
parametersinAdvancedSetup.RefertoChapter1forinformationabouttheflowmeteruser
interface.
To
accesstheBasicSetupmenuinProgrammode:
1> PressP.
2> WhenyouentertheBasicaccesscode,onlyBasicSetupisavailable.PressEtocontinue.
! WARNING !
OUTPUT WILL STOP
Thewarningmessageappearsfollowedbyageneraldescriptionofthemetertype
(eitherinsertionorinline).
METER TYPE IS
INSERTION FLOW
3> PressE.
TAG NAME
>FLOW METER
Thetagnameistheflowmetername.Thename(upto13characters)canindicatethe
location,process,orcompanynamingconvention.
4> PressEtocontinuetothenextoptionwithoutmakingchanges.
Ifyouwanttochangetheflowmetername,pressCtoclearthetagnamefield.Use the
alphanumerickeystoenterlettersandnumbers.PressEtoadvancetothenext
characterposition.PressEtoacceptthenew
nameandcontinuetothenextoption.
FLOW UNITS
>SCMH
^
v
Theflowunitsalsodeterminetheunitsthatappearforvelocityandtemperature.
TheflowrateoptionsareNCMH,NLPM,SCFH,SCFM,SCMH,andSLMP.
ThemassrateoptionsareKGH,KGM,PPH,andPPM.