KurzBSeriesOperationsGuide4–4
Program ModeAdvanced Setup
Option 1 — Basic Setup
BasicflowmetersetupisavailablewithboththeBasicAccesscodeandAdvancedAccesscode.
Note SeeTable12inChapter1foradescriptionofallparameters.
ToaccesstheBasicSetupmenuinProgrammode:
1> PressP.
2> EntertheAdvancedaccesscode,andthenpressE.
3> Press 2toinvoketheQuickJumpoption.
4> Press1fortheBasicSetupmenu,andthenpressE.
! WARNING !
OUTPUT WILL STOP
Thewarningmessageappearsfollowedbyageneraldescriptionofthemetertype
(eitherinsertionorinline).
METER TYPE IS
INSERTION FLOW
5> PressE.
TAG NAME
>FLOW METER
Thetagnameistheflowmetername.Thename(upto13characters)canindicatethe
location,process,orcompanynamingconvention.
6> PressEtocontinuetothenextoptionwithoutmakingchanges.
Ifyouwanttochangetheflowmetername,pressCtoclearthetagname field.Use the
alphanumerickeystoenterlettersandnumbers.PressEtoadvancetothenext
characterposition.PressEtoacceptthenew
nameandcontinuetothenextoption.
FLOW UNITS
>SCMH
^
v
Theflowunitsalsodeterminetheunitsthatappearforvelocityandtemperature.
TheflowrateoptionsareNCMH,NLPM,SCFH,SCFM,SCMH,andSLMP.
ThemassrateoptionsareKGH,KGM,PPH,andPPM.
7> Usethearrow keystoselecttheflowunits,andthenpressE.

Table of Contents

Other manuals for Kurz B Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kurz B Series and is the answer not in the manual?

Kurz B Series Specifications

General IconGeneral
BrandKurz
ModelB Series
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals