KurzB‐SeriesOperationsGuide 4–3
Program ModeAdvanced Setup
Program Mode — Advanced Setup
BeforemakinganyconfigurationchangesinProgrammode,itisimportanttoremember:
Important Youshouldnotmakeanychangestothemeterconfigurationwithouta
completeunderstandingoftheflowmeterparameters.Changingasetting
incorrectlycancausetheflowmetertomalfunction.
• Aflowmeterusedinacriticalprocessorfeedbackcontrolshouldbetakenofflinebefore
makingconfigurationchangesinProgrammode.Somemenuoptionstemporarily
suspendsflowmeteroutputatthelastvaluebeforethemenuoptionwasinvoked.
! WARNING !
OUTPUT WILL STOP
Ifthispromptdoesnotappear,themetercontinuestooperatenormally.
• PressonlyPtocontinuetothenextpromptwithoutmakingchanges.
• Tobackoutofamenu,pressHtoforceanexit.
• AnychangesaccompaniedbythefollowingmessageareautomaticallysavedtoEEPROM
whenProgrammodeisexited.
NEW VALUE
ACCEPTED
Therearenopromptstoconfirmthatyouwanttomakeachange.
• Ifthereisnomenuactivityfor3minutes,thedisplayautomaticallyexitstoRunmode.
• Theconfigurationisretainedthroughflowmeterrebootsandpowercycles.
• TheflowmeteroutputresumeswhenyouexittheAdvancedSetupmenuoption.
OUTPUT UPDATE
IS RESUMED ......